XGN15-12 switchgear

XGN15-12 Switchgear | 12kV Box-Type Fixed AC Metal-Enclosed SF6 Switchgear | GOHO
GOHO XGN15-12 box-type fixed AC metal-enclosed SF6 switchgear
Box-Type MV Switchgear

XGN15-12(F/F·R) Box-Type Fixed AC Metal-Enclosed Switchgear

XGN15-12 series box-type fixed medium voltage switchgear — 12kV, 630A, with SF6 load switch (F) or load switch + fuse combination (F·R). Compact, fully sealed, maintenance-free design ideal for ring main units and prefabricated substation integration. Sealed-for-life SF6 tank with ≤0.1% annual gas leakage rate.

12kV Rated SF6 Load Switch Maintenance-Free Compact RMU
12kV
Rated Voltage
630A
Rated Current
20kA
Short-Time (4s)
IP3X
Protection

Compact SF6 Ring Main Switchgear

Sealed-for-life SF6 load switch technology in a compact box-type enclosure for RMU and prefab substation applications

The XGN15-12(F) and XGN15-12(F·R) box-type fixed AC metal-enclosed switchgear is designed for ring network power supply or radial power supply systems with rated voltage of 12kV and rated current of 630A and below. It is especially suitable for installation in prefabricated substations for control and protection of power distribution systems in urban underground cable networks, industrial parks, and infrastructure projects.

The switchgear features a compact fixed-mounting enclosure with modular construction, integrating SF6 load switches or load switch-fuse combination units within a sealed, maintenance-free stainless steel tank. The FLN36-12D SF6 load switch employs rotary arc extinction technology within a hermetically sealed gas chamber — completely eliminating the need for maintenance over the equipment lifetime, with a gas leakage rate of less than 0.1% per year. Its small footprint and lightweight design make it ideally suited for space-constrained installations.

The "F" designation indicates the load switch variant, while "F·R" denotes the load switch-fuse combination, providing integrated short-circuit protection through current-limiting fuse operation with up to 31.5kA breaking capacity. The striker pin mechanism triggers all three-phase tripping when any single fuse operates, ensuring coordinated protection.

  • 12kV / 630A rating — for secondary distribution and ring main networks
  • Sealed SF6 tank — maintenance-free, ≤0.1% annual gas leakage
  • F / F·R variants — load switch or load switch + fuse combination
  • Compact dimensions — ideal for prefabricated substation integration
  • Spring quick-make mechanism — reliable operation independent of operator speed
  • Mechanical interlocks — prevents incorrect operating sequences
XGN15-12 box-type SF6 switchgear front view

Detailed Parameters

Complete technical specifications for XGN15-12 series box-type fixed switchgear

ParameterSpecification
Rated Voltage12kV
Rated Insulation Voltage12kV
Rated Frequency50Hz / 60Hz
Rated Current (Main Busbar)630A
Rated Short-Time Withstand Current (Icw)20kA (4s)
Rated Peak Withstand Current (Ipk)50kA
Rated Active Load Breaking630A (load switch)
Rated Short-Circuit Making Capacity50kA (peak)
Rated Short-Circuit Breaking (F·R)Up to 31.5kA (via current-limiting fuse)
Busbar SystemRing main / Radial distribution
Degree of ProtectionIP3X (enclosure)
Installation TypeIndoor, fixed, prefab substation-integrated
Switching Device (F)FLN36-12D SF6 load switch
Switching Device (F·R)FLRN36-12D load switch + fuse combination
Operating MechanismManual spring-charged quick-make/quick-break (standard) / Electric motor (optional)
Mechanical Endurance≥ 5,000 operations (load switch)
SF6 Gas Pressure (20°C)1.4 bar (absolute)
Gas Leakage Rate≤ 0.1% per year (sealed for life)
Maintenance IntervalSealed for life — maintenance-free
Fuse Type (F·R)HV current-limiting fuse with striker pin
Cable TerminationHeat shrink / Cold shrink / Plug-in separable connectors
Ambient Temperature-25°C to +40°C
Ambient Humidity≤ 95% (non-condensing)
Altitude≤ 1000m (derated above)
StandardsGB 3804, GB 16926, IEC 62271-103, IEC 62271-105

Why Choose XGN15-12 Switchgear

Sealed SF6 technology in a compact, maintenance-free package for reliable distribution

Sealed SF6 Load Switch

FLN36-12D SF6 load switch features rotary arc extinction within a hermetically sealed stainless steel tank — completely maintenance-free with no gas handling required over the equipment lifetime (leakage rate < 0.1% per year).

Ring Network Optimized

Specifically designed for 12kV ring main unit (RMU) and radial distribution systems, supporting both looped and open-ring operating configurations common in urban underground cable networks.

Integrated Fuse Protection

The F·R load switch + fuse combination variant provides high short-circuit breaking capacity (up to 31.5kA through the fuse) while maintaining compact enclosure dimensions — striker pin triggers three-phase tripping.

Prefab Substation Ready

Small dimensions and lightweight construction make it the preferred HV switching and protection device for installation inside prefabricated box-type substations, container substations, and outdoor distribution cabinets.

Maintenance-Free Operation

All primary components are sealed within the SF6 tank, eliminating the need for periodic servicing — no contact replacement, no insulation cleaning, no lubrication required over the product service life.

Quick Operating Mechanism

Spring-charged quick-make / quick-break mechanism ensures specified making and breaking speeds independent of operator action speed, with clear position indication visible through the panel window.

Reliable Interlocking

Mechanical interlocks between the load switch, earthing switch, and panel door prevent incorrect operating sequences — the panel door cannot be opened with the load switch closed, and the earthing switch cannot be closed with the load switch closed.

Versatile Cable Options

Supports a wide range of cable termination types — heat shrink, cold shrink, and plug-in separable connectors up to 630A rated current — accommodating different cable specifications and installation preferences.

IEC & GB Compliant

Fully type-tested and compliant with GB 3804, GB 16926, IEC 62271-103 (load switches), and IEC 62271-105 (load switch-fuse combinations) — ensuring reliable performance and international acceptance.

Where XGN15-12 Excels

Compact SF6 switchgear for diverse secondary distribution and RMU applications

Urban RMU Networks

10kV underground cable ring main distribution

Prefab Substations

HV switching in box-type compact substations

Secondary Distribution

Industrial & commercial secondary substations

Renewable Energy

Wind & solar farm collection systems

Residential MV

Community medium voltage distribution

Infrastructure

Tunnels, airports, railways, highways

Industrial Parks

Industrial park distribution & metering

Outdoor Cabinets

Outdoor cabinet-type secondary distribution

Quality & Compliance

Type-tested and certified for reliable medium voltage load switching performance

IEC 62271-103

Load switches & disconnectors standard

IEC 62271-105

Load switch-fuse combinations

ISO 9001

Quality management system

Type Tested

Full electrical performance type testing

Frequently Asked Questions

Common questions about XGN15-12 box-type SF6 switchgear

What's the difference between the F and F·R variants of XGN15-12?

The "F" variant (XGN15-12(F)) is equipped with an SF6 load switch (FLN36-12D) — it can switch load currents (up to 630A) and provide isolation, but it does not provide short-circuit protection on its own. It's typically used in conjunction with upstream protective devices like circuit breakers or fuses. The "F·R" variant (XGN15-12(F·R)) is equipped with a load switch-fuse combination unit (FLRN36-12D) — it combines load switching capability with high-voltage current-limiting fuses that provide short-circuit protection up to 31.5kA. When any single fuse operates, a striker pin mechanism triggers all three-phase tripping of the load switch, ensuring coordinated protection. Choose F when short-circuit protection is provided elsewhere in the system; choose F·R when you need integrated short-circuit protection in a compact package.

How is XGN15-12 different from HXGN15-12 RMU?

Both use SF6 load switch technology but serve different applications. The XGN15-12 is a box-type fixed metal-enclosed switchgear designed primarily for installation inside prefabricated substations, distribution cabinets, and indoor switchrooms — it's a single-panel unit with incoming/outgoing feeders. The HXGN15-12 is a dedicated ring main unit (RMU) configured with multiple SF6 insulated compartments (typically 2-3 ways: 2 incoming + 1 transformer feeder or similar) in a compact, standalone enclosure designed for direct installation in urban underground cable ring networks. XGN15-12 offers more flexible current ratings and component options within its enclosure, while HXGN15-12 is optimized specifically for ring network configurations with standard 2-way or 3-way layouts. Both are maintenance-free and use similar SF6 switching technology.

Is the SF6 gas in the XGN15-12 really maintenance-free?

Yes, the SF6 gas tank in the XGN15-12 is hermetically sealed and designed for maintenance-free operation over the equipment lifetime. The stainless steel tank is welded and precision-manufactured to achieve a gas leakage rate of less than 0.1% per year — well below the IEC standard requirement. At this leakage rate, the gas pressure remains within specification for more than 30 years, which exceeds the typical service life of the switchgear. Unlike older designs that required periodic gas top-ups and leak checks, the sealed-for-life design eliminates the need for routine gas maintenance. However, we recommend a visual inspection of the gas density monitor (if equipped) during regular plant maintenance walkthroughs as a precautionary measure. For applications requiring gas monitoring, we can supply density gauges or pressure sensors as options.

Can XGN15-12 be used in outdoor installations?

The XGN15-12 itself is rated IP3X and designed for indoor installation. It is not weatherproof and should not be directly exposed to the elements. However, it is very commonly used in outdoor applications when installed inside a weatherproof enclosure — such as a prefabricated box-type substation (YBM/ZBW), a container substation, or an outdoor distribution cabinet. In fact, one of its primary design purposes is integration into prefabricated substation enclosures, where it serves as the medium voltage switching and protection unit. For outdoor installations, we recommend specifying one of our prefabricated substation solutions with the XGN15-12 integrated inside, which provides proper weather protection, ventilation, and thermal management. If you need a standalone outdoor RMU, please consider our HXGN15-12 series which is designed for direct outdoor installation in stainless steel enclosures.

How do I select the right fuse rating for the F·R variant?

Fuse selection for the F·R variant depends on the protected equipment and the available fault current. For transformer protection, the fuse rating is typically selected at 1.5–2 times the transformer's full-load current to accommodate inrush current while providing adequate short-circuit protection. Standard fuse ratings available include 10A, 16A, 25A, 31.5A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, and 200A for 12kV systems. Important considerations include: the fuse must be rated for the system voltage, its breaking capacity must exceed the available short-circuit current at the point of installation, and its time-current characteristic must coordinate with upstream and downstream protective devices. The striker pin must be compatible with the load switch mechanism to ensure proper tripping. We can help you select the correct fuse rating based on your specific application — just provide the transformer size, available fault current, and coordination requirements.

What safety interlocks does the XGN15-12 have?

The XGN15-12 is equipped with a comprehensive mechanical interlocking system to prevent incorrect operating sequences and protect personnel. Key interlocks include: (1) Load switch – earthing switch interlock: the earthing switch cannot be closed unless the load switch is in the open position, and the load switch cannot be closed when the earthing switch is closed — this prevents dangerous back-feeding. (2) Panel door interlock: the panel door cannot be opened when the load switch is in the closed position, and the load switch cannot be closed when the door is open — ensuring personnel cannot access live parts during operation. (3) Fuse compartment interlock (F·R variant): prevents access to the fuse compartment when the switch is energized. (4) Position indication: clear visible indicators show the switch position (ON/OFF/EARTH) through the front panel window. These interlocks are purely mechanical — no auxiliary power required — ensuring they remain functional even under loss-of-control-power conditions.

Need Compact SF6 Switchgear for RMU?

Send us your system requirements — voltage, current, short-circuit rating, and configuration. We'll configure the right XGN15-12 solution, including F or F·R variants and fuse ratings.