Low Voltage · Intelligent Air Circuit Breaker

GHW3
Intelligent Air Circuit Breaker

GOHO® builds the GHW3 intelligent air circuit breaker as the main protective device of a low voltage switchboard. It is offered in four frame sizes from 630 A to 6300 A at 400 V and 690 V, in drawout or fixed construction, with an intelligent controller in place of the older thermal‑magnetic releases. The controller carries long‑time, short‑time, instantaneous and earth‑fault protection, and on the communication version it reports to a supervisory system over Modbus or Profibus. It is used as the incoming breaker of a main switchboard, as a generator main breaker and as a bus tie where full time grading with the downstream moulded case breakers is required.

  • Rated voltage 400 / 690 V
  • Rated current 630—6300 A
  • Breaking capacity up to 120 kA
  • Drawout or fixed
GHW3 intelligent air circuit breaker manufactured by GOHO Electric — drawout type low voltage frame circuit breaker with the intelligent controller display, the open and close push buttons and the manual charging handle on the front panel.
Rated Operational Voltage
400 / 690 V Three-phase, 50 / 60 Hz, utilization category B
Rated Current
630 · 800 · 1000 … 6300 A Four frame sizes: 2000, 3200, 4000, 6300 A
Breaking Capacity
Icu 80 · 100 · 120 kA At 400 V; 50 · 65 · 85 kA at 690 V

Technical Specifications

The GHW3 is a four‑frame family. Because the frame sizes are stepped rather than continuous, the first decision in selecting one is the frame, and the current rating is then chosen inside that frame.

ParameterValue
Rated operational voltage UeAC 400 V / 690 V
Rated insulation voltage Ui800 V
Rated impulse withstand voltage Uimp8000 V
Rated frequency50 / 60 Hz
Number of poles3 / 4
Frame sizes2000 / 3200 / 4000 / 6300 A
Rated current In630 · 800 · 1000 · 1250 · 1600 · 2000 · 2500 · 3200 · 4000 · 5000 · 6300 A
Utilization categoryB
Rated ultimate short-circuit breaking capacity Icu at 400 V80 / 100 / 100 / 120 kA
Rated ultimate short-circuit breaking capacity Icu at 690 V50 / 65 / 65 / 85 kA
Rated service short-circuit breaking capacity Ics at 400 V65 / 80 / 80 / 100 kA
Rated service short-circuit breaking capacity Ics at 690 V50 / 50 / 65 / 75 kA
Rated short-time withstand current Icw, 0.4 s, at 400 V50 / 65 / 80 / 100 kA
Rated short-time withstand current Icw, 0.4 s, at 690 V40 / 50 / 65 / 75 kA
Total break time≤ 20 – 30 ms
Total closing time≤ 55 – 70 ms
Operating frequency20 operations per hour
Rated current of the neutral pole50 % or 100 % of In, to order
MountingDrawout type or fixed type
Drawout positionsConnected / test / disconnected, with mechanical safety interlocks
Intelligent controllerType L (economy) / M (standard intelligent) / H (communication)
Protection functionsLong-time delay (overload), short-time delay, instantaneous and earth fault — four-stage LSIG
Metering and memoryCurrent and voltage display, load monitoring, thermal memory, fault recording, self-test
CommunicationModbus-RTU / Profibus-DP on the communication controller
Auxiliary equipmentShunt release, undervoltage release (instantaneous or delayed), closing electromagnet, auxiliary contacts, mechanical interlock, key lock
Electrical endurance1000 / 500 operations depending on frame
Mechanical endurance10 000 / 5000 operating cycles depending on frame
Permissible ambient temperature−5 °C to +40 °C (24 h mean ≤ +35 °C)
Product standardGB/T 14048.2 · IEC 60947-1 · IEC 60947-2

Breaking capacities are quoted frame by frame in the table below. The values above show the range covered by the four frames; the exact Icu and Ics of the breaker offered is confirmed on the datasheet issued with the quotation, because the service breaking capacity depends on the frame, the controller fitted and the cable connection arrangement.

Frame Sizes & Breaking Capacity

The four frames are stepped so that the frame is chosen first and the current rating inside it second. A frame carries any current rating listed for it, and the breaking capacity is fixed by the frame.

FrameRated current InIcu at 400 VIcs at 400 VIcw, 0.4 s, at 400 VIcu at 690 V
2000 A400 – 2000 A80 kA65 kA50 kA50 kA
3200 A2000 – 3200 A100 kA80 kA65 kA65 kA
4000 A3200 – 4000 A100 kA80 kA65 – 80 kA65 kA
6300 A4000 – 6300 A120 kA100 kA85 – 100 kA85 kA

Inside each frame the current rating is set by the controller setting and the current transformers fitted, not by a different breaker. A 2000 A frame, for example, covers 400 A through 2000 A, so a switchboard can be ordered with the frame sized for the eventual load and the rating set to the present one.

Service Conditions

A low voltage air circuit breaker works inside a switchboard, so the ambient temperature inside the enclosure, the pollution degree and the prospective short-circuit current at the incoming terminals are the conditions that matter.

ConditionLimits for standard supply
Ambient temperature−5 °C to +40 °C
Average ambient temperature over 24 hours≤ +35 °C
Altitude≤ 2000 m
Relative humidity≤ 95 % at +25 °C, with condensation avoided by ventilation or a heater
Pollution degree3
Installation categoryIII / IV
Rated impulse withstand voltage8000 V, referred to 2000 m altitude
Seismic intensity≤ 8 degrees
InstallationIndoor, inside a switchboard or an enclosure; no explosive or corrosive atmosphere, no conductive dust, no violent vibration

Inside a closed switchboard the air temperature is typically 10 to 15 K above the room temperature. Where the calculated internal temperature exceeds +40 °C, the breaker is derated or the enclosure is ventilated — the offer states which, so that the continuous rating is not read from the wrong table.

Construction & Operating Principle

Drawout construction with three positions

The drawout version runs on rails inside the switchboard between a connected, a test and a disconnected position. The primary contacts are separated and the secondary plug is still engaged in the test position, so the breaker can be operated and its protection checked without exposing the operator to the live busbar. In the disconnected position the breaker can be lifted out and replaced from stock, which is the practical reason a main incoming breaker is usually specified as drawout: a fault in the incomer does not have to take the switchboard out of service.

Contact system and arc control

Each pole carries a main contact and an arcing contact with a splitter plate stack behind them. When the breaker opens, the arc is driven magnetically into the stack and is divided into short arcs that extinguish between the plates, and the whole process takes place inside the arc chamber. Because the arc is contained, the breaker has no external arc flash at the front of the switchboard, which is what allows the switchboard doors to be closed during operation.

Operating mechanism

The mechanism uses a closing spring charged by a motor and an opening spring. Manual charging with the handle is provided for maintenance and for use with the control supply removed. Opening is initiated by the shunt release or by the controller's trip coil; an undervoltage release is available where the breaker has to open on loss of supply as well.

Intelligent controller

The controller replaces the thermal and magnetic releases and the separate protection relay of an older design. Current transformers built into the breaker measure each phase and the neutral, and the controller evaluates them in a microprocessor against the protection settings. Because the settings are digital, the grading between the incoming breaker and the outgoing moulded case breakers can be calculated and set rather than adjusted by trial.

Intelligent air circuit breaker controller panel showing the current and voltage display, the four-stage protection setting keys and the open and close push buttons.
Intelligent controller on the breaker front. The display shows the measured current and voltage, the setting keys set the four protection stages, and the push buttons open and close the breaker from the switchboard front.
Air circuit breaker with the communication type controller, showing the measurement display and the setting interface used for remote monitoring and control.
Communication controller. The communication version adds a port for remote measurement, remote adjustment, remote control and remote signalling, so the incomer can be monitored and operated from a supervisory system.

Intelligent Controller & Protection Functions

Three controller types

The controller is offered in three levels so that the cost matches the duty. The economy type offers the basic protection stages set by DIP switches, without a digital display. The standard intelligent type adds protection, measurement, display and alarm functions. The communication type adds the port and the protocols. Because the controller is a separate module, a standard or economy breaker can be upgraded later without replacing the breaker.

Four-stage protection

Long-time delay handles overload with a thermal memory so that a breaker that has just carried an overload trips sooner on the next one. Short-time delay provides the adjustable time grading with the downstream breakers. Instantaneous protection clears a close-up short circuit. Earth fault protection covers single-phase earth faults, with an adjustable setting and a choice of residual or source earth connection. Parameters are set by rotary dial or by keypad and are readable on the display.

Measurement and memory

The controller displays current and voltage, monitors loading, keeps a thermal image of the load, records the last fault with its values, and runs a self-test. That record is what makes a post-fault investigation possible without fitting a separate analyser: the tripping current, the phase involved and the protection stage that operated are all stored.

Selectivity and coordination

The short-time withstand current rating is what makes grading possible. A 6300 A frame holds 85 to 100 kA for 0.4 second, which is long enough for the downstream moulded case breaker to clear a fault in its own zone while the incomer waits. Without that withstand capability the incomer would have to trip instantaneously and the whole board would go dark. The same logic runs one level down between the GHM3 moulded case breakers and the DZ47 miniature breakers on the final circuits.

Accessories and interlocks

A shunt release provides remote electrical tripping, an undervoltage release opens the breaker when the supply is lost (instantaneous or delayed), a closing electromagnet works with the motor mechanism, and auxiliary contacts report the position. A mechanical interlock prevents two incoming breakers from being closed onto the same busbar at the same time, and a key lock holds the breaker open for maintenance.

Frame Sizes & Options

The frame size is set by the prospective short-circuit current at the incoming terminals and by the continuous current the board has to carry, including any planned growth.

Frame 2000 A In 400 – 2000 A · Icu 80 kA at 400 V

The usual frame for a distribution board incomer and for a generator main breaker in the low hundreds of kVA. Covers a wide current range on one frame, so a board can be built for a load that is expected to grow.

Frame 3200 A In 2000 – 3200 A · Icu 100 kA at 400 V

For a main switchboard incomer in a large commercial building, a data centre or an industrial plant, where the transformer secondary current sits in the 2000 to 3200 A band.

Frame 4000 A In 3200 – 4000 A · Icu 100 kA at 400 V

Used where two transformers run in parallel on one busbar, or where a single large transformer feeds the board directly. The higher short-time withstand current is what allows full grading with the outgoing breakers.

Frame 6300 A In 4000 – 6300 A · Icu 120 kA at 400 V

The top frame, for a heavy industrial incomer, a large generator main breaker or a bus tie between two main boards. Supplied only against a system study because the busbar and the cable connections have to be designed for it.

OptionAvailable
Poles3-pole or 4-pole
Neutral pole rating50 % or 100 % of In, to order
MountingDrawout type with three positions, or fixed type
ControllerType L (economy) / M (standard intelligent) / H (communication)
Communication protocolModbus-RTU or Profibus-DP on the communication controller
Shunt releaseFor remote electrical tripping
Undervoltage releaseInstantaneous or delayed action
Closing electromagnetOperates with the motor-charged mechanism
Auxiliary and alarm contactsFor position indication and signalling
Mechanical interlock and key lockFor bus ties and for maintenance lockout

A frame is quoted against the prospective short-circuit current at the incoming terminals and the busbar rating, not against the transformer rating alone. Send the system study values with the enquiry and the frame, the breaking capacity and the controller type are confirmed together.

Key Features

Four Frames From 630 A To 6300 A One breaker family covers a distribution board incomer and a 6300 A bus tie. Inside a frame the current rating is set by the controller and the current transformers, so a board can be ordered with the frame sized for the eventual load and the rating set to the present one.
Drawout With Three Positions The drawout version gives connected, test and disconnected positions with mechanical interlocks. A faulty incomer is exchanged from stock rather than repaired in place, which is what keeps a main switchboard in service through a breaker failure.
Breaking Capacity Up To 120 kA Icu reaches 120 kA at 400 V on the 6300 A frame and 85 kA at 690 V, with a service breaking capacity Ics of 100 kA. That covers the prospective fault current of a large transformer close to the switchboard.
Short-Time Withstand For Full Grading Icw is 50 to 100 kA for 0.4 second depending on frame. Holding the fault for that long is what lets the downstream breaker clear its own zone while the incomer waits, so a fault on one outgoing circuit does not take the whole board down.
Four-Stage LSIG Protection Long-time delay with thermal memory, short-time delay for grading, instantaneous for close-up faults and earth fault protection for single-phase earth faults. All four stages are set independently and are readable on the display.
Interchangeable Intelligent Controller The controller is a module on the front of the breaker. Economy, standard and communication types share the mounting, so the protection level can be raised later without changing the breaker, the busbar or the enclosure.
Communication-Ready The communication controller reports measurement, position and fault records over Modbus-RTU or Profibus-DP. Remote measurement, remote adjustment, remote control and remote signalling are all available without an additional transducer set.
Routine-Tested Before Dispatch Every breaker passes a main-circuit resistance measurement, a power-frequency withstand test of the main and auxiliary circuits, a controller setting and trip test at the ordered values, and a full mechanical operating sequence. Test records travel with the breaker.

Applications

The GHW3 is used wherever a low voltage system needs a main protective device with a high breaking capacity and adjustable grading against the breakers downstream.

  • Main switchboard incomer in industrial plants and large commercial buildings
  • Transformer secondary main breaker at the LV side of a distribution substation
  • Generator main breaker and generator control panel incomer
  • Bus tie between two main switchboards or between two transformer secondaries
  • Motor control centre incomer where several large motors start together
  • Data centre and telecom room main distribution, where selectivity is essential
  • Photovoltaic and wind plant LV collector incomer and inverter main breaker
  • Mining, steel, cement and paper plants — heavy industrial incomers
  • Marine and offshore installations, including 690 V distribution
  • Hospitals, airports and rail installations, where an unnecessary trip is not acceptable
  • Electric vehicle charging hubs — the incomer of a charging park
  • Switchboard refurbishment — replacing an existing main breaker with the same panel opening

What We Need to Quote Your Breaker

The frame, the breaking capacity and the controller are chosen together against the system study. With the items below we can return a firm quotation and a dimension drawing for the panel opening.

  • System voltage, rated frequency and the earthing arrangement
  • Transformer rating and impedance, or the busbar continuous current required
  • Prospective short-circuit current at the incoming terminals — this sets the frame
  • Number of poles and whether the neutral has to be fully rated
  • Controller type required — economy, standard intelligent or communication
  • Protection settings or the grading study, if already calculated
  • Mounting — drawout or fixed, and the panel opening dimensions
  • Accessories — shunt release, undervoltage release, closing coil, auxiliary contacts, interlock; control voltage and quantity

Send these to gohointl@gmail.com and we will reply with a priced offer, the dimensional drawing for the panel opening, the controller setting list and the routine test plan for the breaker.

Standards & Documentation

ItemReference
Product standard, ChinaGB/T 14048.2 — Low-voltage switchgear and controlgear, circuit-breakers
Product standard, internationalIEC 60947-2 — Low-voltage switchgear and controlgear, Part 2: Circuit-breakers
General rules, internationalIEC 60947-1 — Low-voltage switchgear and controlgear, general rules
Routine test, main circuitMain circuit resistance measurement and power-frequency withstand test
Routine test, auxiliary circuitsWiring check and power-frequency withstand test of the control and auxiliary circuits
Routine test, protectionController setting and trip test at the ordered values for each protection stage
Routine test, mechanicalFull open / close operating sequence, drawout racking check and interlock check
Documentation suppliedDimensional drawing for the panel opening, controller setting record, routine test record and operating instructions

Type test reports for the GHW3 platform and the routine test record for the individual breaker are available for project qualification on request.

GHW3 air circuit breaker series range showing the four frame sizes of the intelligent low voltage air circuit breaker family, from the 2000 A frame to the 6300 A frame.
The four frames as one family. Frame sizes 2000, 3200, 4000 and 6300 A share the controller, the accessories and the operating mechanism, which is why an existing panel opening can usually be re‑used when a board is rebuilt.

Breakers are assembled in our own factory in Yueqing, Zhejiang — the same site that builds our switchgear, transformers and prefabricated substations. Contact assembly, controller fitting and calibration, wiring and routine testing all happen in‑house, which keeps both the delivery schedule and the quality check inside our control.

Need a GHW3 air circuit breaker for your main switchboard?
Get a Quote

GOHO® is a registered trademark of Gonghong Electric Appliance Co., Ltd. Technical data describes the standard GHW3 intelligent air circuit breaker platform and is given as typical ratings; the ratings of a specific unit follow the approved drawing and the configuration ordered. Ratings outside the table in this page, and site conditions outside the stated limits, are quoted on application. Product images are shown for illustration. Please refer to the drawing issued with your offer for dimensional and foundation data.

Scroll to Top