Medium Voltage · Outdoor Pole Mounted Vacuum Circuit Breaker

ZW32 Series
Outdoor Vacuum Circuit Breaker, 10 kV to 40.5 kV

GOHO® builds the ZW32 as one outdoor pole‑mounted platform in three voltage classes – 12 kV, 24 kV and 40.5 kV – so that a 10 kV rural feeder, a 20 kV urban network and a 35 kV industrial line are switched by the same column construction, the same spring mechanism and the same set of spare parts. Each phase is a separate solid‑insulated column carrying its own vacuum interrupter, and the three columns are bolted to a common steel frame with the spring mechanism below. Keeping the phases apart in separate columns is what gives the ZW32 its breaking capability and its generous phase spacing: about 340 mm in the 12 kV class, 380 mm in the 24 kV class and about 460 mm in the 40.5 kV class. The breaker switches load current, overload current and short‑circuit current on overhead networks, at pole substations and at industrial site incomers, and it is supplied plain, with an integral isolating function, or with a controller for automated sectioning and reclosing.

  • Three voltage classes — 12, 24 and 40.5 kV
  • Rated normal current 630—1600 A
  • Breaking capacity 16—31.5 kA
ZW32 series outdoor pole mounted high voltage vacuum circuit breaker built by GOHO Electric — three separate solid insulated interrupter columns on a steel mounting frame with the spring operating mechanism and the open close indicator below.
Voltage Classes
12 · 24 · 40.5 kV For 10 kV, 20 kV and 35 kV systems
Rated Normal Current
630 · 1250 · 1600 A One frame, rated to order
Short-Circuit Breaking
16 · 20 · 25 · 31.5 kA Peak making 40 · 50 · 63 · 80 kA, 4 s duty

Technical Specifications

The table below puts the three voltage classes side by side, because that is how a ZW32 is actually chosen: the system voltage fixes the class, and the class fixes the insulation levels, the phase spacing and the contact travel. Everything else – current rating, breaking capacity, current transformers, isolator, controller – is selected inside the class. Where a value differs with the configuration ordered, the full range is given and the figure that applies is confirmed on the approved drawing.

Parameter12 kV class24 kV class40.5 kV class
Rated voltage Ur12 kV24 kV40.5 kV
Rated frequency50 Hz50 Hz50 Hz
Number of poles333
Rated normal current Ir630 / 1250 A630 / 1250 A630 / 1250 / 1600 A
Rated short-circuit breaking current Isc16 / 20 / 25 kA20 / 25 kA20 / 25 / 31.5 kA
Rated short-circuit making current (peak)40 / 50 / 63 kA50 / 63 kA63 / 80 kA
Rated peak withstand current Ip40 / 50 / 63 kA50 / 63 kA63 / 80 kA
Rated short-time withstand current Ik, 4 s16 / 20 / 25 kA20 / 25 kA20 / 25 / 31.5 kA
Rated duration of short circuit4 s4 s4 s
Rated operating sequenceO – 0.3 s – CO – 180 s – COO – 0.3 s – CO – 180 s – COO – 0.3 s – CO – 180 s – CO
Power-frequency withstand voltage, 1 min (dry) — phase to earth and phase to phase42 kV65 kV95 kV
Power-frequency withstand voltage, 1 min (dry) — across the isolating gap48 kV79 kV95 kV
Power-frequency withstand voltage, 1 min (wet) — phase to earth and phase to phase34 kV50 kV80 kV
Lightning impulse withstand voltage (peak) — phase to earth and phase to phase75 kV125 kV185 kV
Lightning impulse withstand voltage (peak) — across the isolating gap85 kV145 kV185 kV
Power-frequency withstand voltage, secondary circuit, 1 min2 kV2 kV2 kV
Rated short-circuit breaking operations303030
Rated current breaking operations10 00010 00010 000
Contact gap9 ± 1 mm12 ± 1 mm16 ± 1 mm
Contact overtravel (contact spring compression)2 ± 0.5 mm3 ± 1 mm3 ± 0.5 mm
Average opening speed1.2 ± 0.2 m/s1.4 ± 0.2 m/s1.4 – 1.8 m/s
Average closing speed0.6 ± 0.2 m/s0.8 ± 0.2 m/s0.4 – 0.8 m/s
Contact bounce time on closing≤ 2 ms≤ 2 ms≤ 5 ms
Three-phase opening / closing asynchronism≤ 2 ms≤ 2 ms≤ 2 ms
Interphase centre distance340 ± 1.5 mm380 ± 1.5 mm460 ± 2 mm
Main circuit resistance per phase — without isolator≤ 80 µΩ≤ 80 µΩ≤ 80 µΩ
Main circuit resistance per phase — with isolator≤ 120 µΩ≤ 120 µΩ≤ 150 µΩ
Opening time≤ 50 ms≤ 50 ms≤ 60 ms
Closing time≤ 60 ms≤ 60 ms≤ 100 ms
Rated control voltageDC 220 V / DC 110 V, AC 220 VDC 220 V / DC 110 V, AC 220 VDC 220 V / DC 110 V, AC 220 V
Energy-storage motorDC 220 V / 110 V, charging time ≤ 8 sDC 220 V / 110 V, charging time ≤ 8 sDC 220 V / 110 V, charging time ≤ 8 s
Permissible contact wear (accumulated thickness)3 mm4 mm3 mm
Specific creepage distance≥ 31 mm/kV, Class IV≥ 31 mm/kV, Class IV≥ 31 mm/kV, Class IV
Mechanical endurance, spring mechanism10 000 operating cycles10 000 operating cycles10 000 operating cycles
Weight, complete with operating mechanismapprox. 100 kg
(about 140 kg with isolator)
approx. 150 kgapprox. 320 kg
Product standardGB/T 1984 · IEC 62271-100GB/T 1984 · IEC 62271-100GB/T 1984 · IEC 62271-100

Values above describe the standard ZW32 platform and are given as typical ratings. The rating combination of a specific breaker follows the approved drawing, the current transformers fitted and the operating mechanism ordered. Operation at 60 Hz, other control voltages, a higher current rating inside a class, heavier pollution, higher altitude and an integral isolating switch are all quoted on application. The weights exclude the pole‑top frame and the controller.

Reading The Model Code

A ZW32 is ordered by its designation, so the designation is worth reading as three separate decisions: the voltage class, the current and breaking rating, and the options.

ElementMeaning
ZW32Outdoor pole-mounted vacuum circuit breaker with three separate interrupter columns
- 12 / - 24 / - 40.5Rated voltage in kV — the voltage class. The 12 kV class serves 10 kV systems, the 24 kV class serves 20 kV systems and the 40.5 kV class serves 35 kV systems.
/ TSpring stored-energy operating mechanism. The / M suffix denotes a permanent-magnet mechanism where that version is ordered.
630 / 1250 / 1600Rated normal current in A
- 20 / - 25 / - 31.5Rated short-circuit breaking current in kA
/ GIntegral isolating function, giving a visible break and mechanically interlocked with the breaker position
intelligentSupplied with a controller for remote measurement, signalling, control and adjustment, automatic reclosing and fault sectioning

A typical order therefore reads ZW32‑24/T1250‑25/G: 24 kV class, spring mechanism, 1250 A, 25 kA, with an integral isolating function. Because the designation carries the rating, it is the string we quote against and the string that is stamped on the nameplate.

Service Conditions

The ZW32 stands on an outdoor frame with its insulators exposed, so the external insulation is sized against the pollution level and the altitude rather than against the interrupting duty. The envelope below applies to all three voltage classes.

ConditionLimits for standard supply
Ambient temperature−30 °C to +40 °C
Altitude≤ 1000 m, higher on request
Wind pressure≤ 700 Pa (equivalent to 34 m/s)
Air pollution levelClass IV, specific creepage distance 31 mm/kV or more
Ice coating thickness≤ 10 mm
Relative humidity, daily mean≤ 95 %
Seismic intensity≤ 8 degrees
InstallationOutdoor, pole-mounted on a steel frame or standing on a platform frame, mounted level and secure
Mechanism enclosureSealed mechanism box with an anti-condensation heater for humid, coastal and polluted sites
Manual operationManual energy storage and a manual emergency opening device, both usable with the control supply removed

Sites outside these limits — high altitude, a lower minimum temperature, heavier ice loading or a different pollution class — are handled by agreement at the enquiry stage, because the creepage distance of the columns, the phase spacing and the mechanism heater are all selected against them. The 12 kV class is routinely built for altitudes up to 2000 m; above 1000 m the 24 kV and 40.5 kV classes are re-rated for the reduced dielectric strength of air.

Available Voltage Classes

The same column construction, the same spring mechanism and the same frame drawing are used across the three classes, so the spare-parts list and the operating procedure stay the same as a network grows from 10 kV to 35 kV. What changes between the classes is the insulation level, the phase spacing and the contact travel.

ZW32‑12 12 kV · 630–1250 A · 16–25 kA

The 10 kV class and by far the most widely used one. Line switching, feeder protection and sectioning on rural and urban 10 kV overhead networks, and the class in which distribution automation is most often deployed. Also built for 2000 m altitude and for automatic reclosing with a sectionalising controller.

ZW32‑24 24 kV · 630–1250 A · 20–25 kA

The 20 kV class, for networks that have moved up from 10 kV to carry more load over the same right of way. Its wider phase spacing and larger interrupter assembly give it the higher breaking capability that a 20 kV system short-circuit level demands.

ZW32‑40.5 40.5 kV · 630–1600 A · 20–31.5 kA

The 35 kV class, built in the same compact solid-insulated construction as the 12 kV class rather than in the porcelain-column arrangement of a conventional 40.5 kV outdoor breaker. That makes it far lighter than a porcelain-column unit and considerably quicker to install on a pole or on a platform frame.

OptionAvailable
Rated normal current630 A / 1250 A, and 1600 A in the 40.5 kV class
Rated short-circuit breaking current16 / 20 / 25 kA in the 12 kV class, 20 / 25 kA in the 24 kV class, 20 / 25 / 31.5 kA in the 40.5 kV class
Operating mechanismSpring stored-energy mechanism with manual or motor charging; permanent-magnet mechanism on request
Current transformers2 or 3, one per phase, mounted on the interrupter columns; ratios 200/5, 400/5 and 600/5 A to order, with protection or metering cores
Isolating functionNot fitted, or integral with a visible break and a mechanical interlock
Control voltageDC 220 V / DC 110 V, AC 220 V
Energy-storage motorDC 220 V / 110 V, charging time ≤ 8 s
AutomationController for remote measurement, signalling, control and adjustment, automatic reclosing and fault sectioning
MountingPole-mounted on a steel frame, or standing on a platform frame

Transformer ratios, the controller interface and the mounting frame are project items. The column arrangement, the outline drawing and the secondary circuit diagram are issued with the offer once the transformer ratios are fixed.

Construction & Operating Principle

The three classes share one mechanical architecture, so the description below applies to a ZW32 whatever its class; the figures that change with the class are the phase spacing and the contact travel given in the table above.

Three separate interrupter columns

Each phase is built as an independent column: a vacuum interrupter held inside a solid‑insulated cylinder, with the incoming and outgoing terminals brought out at the top and the bottom of the same column. The three columns stand on a common steel frame at a fixed phase spacing – about 340 mm in the 12 kV class, 380 mm in the 24 kV class and about 460 mm in the 40.5 kV class. Keeping the phases in separate columns rather than in one tank raises the dielectric clearance available between phases and lets the interrupter assembly be larger, which is how the ZW32 reaches its breaking capability at each voltage.

Solid insulation, no oil and no gas

The interrupter is enclosed in a cast epoxy cylinder produced by vacuum casting, with the external sheds either cast into the same part or covered with a silicone rubber housing for coastal and heavily polluted sites. The interrupter itself breaks in vacuum. There is no oil to test or replace and no insulating gas to monitor or top up, so the only routine work on the breaker is a visual check and an operating test.

Drive linkage and spring mechanism

The three insulating pull rods are driven from a common shaft through a linkage, so the three poles open and close together inside the asynchronism limit. The spring mechanism, housed in a sealed box on the frame, stores the closing energy; it is charged by the energy-storage motor and, for commissioning or where the control supply is not available, by hand. Opening is driven by the opening spring in the mechanism, and a manual emergency opening device is fitted as standard.

Optional isolating function

The ZW32 can be supplied with an isolating function so that the unit also provides a visible break. The column arrangement is then extended so that the open position gives an isolating distance that satisfies the across-the-gap withstand values in the table above, and the mechanism indicates the position. The feature is identified in the type designation and is mechanically interlocked with the breaker position, so it cannot be operated with the breaker closed. Surge arresters can be mounted on the same frame.

ZW32 series outdoor vacuum circuit breaker showing the three solid insulated interrupter columns with the terminals and the built-in current transformer rings at the top of each column.
Interrupter columns with built-in transformers. Each phase carries its own interrupter in a solid-insulated column; the current transformer ring sits around the primary connection at the top of the column, so no separate CT pedestal is needed.
ZW32 series three-pole outdoor vacuum circuit breaker on its steel mounting frame, showing the phase spacing and the operating linkage below the frame.
Frame and phase spacing. The three columns stand on a common steel frame at a fixed phase spacing that increases with the voltage class. The drive linkage that ties the three poles together runs under the frame, and the mechanism box carries the spring charger, the coils and the auxiliary switches.

Current Transformers, Isolating Function & Automation

Built-in current transformers

Two or three current transformers can be fitted on the breaker, one per phase, mounted around the primary connection at the top of each interrupter column. Typical ratios are 200/5, 400/5 and 600/5 A, selected to the line loading, and a dual-winding transformer can serve metering and protection from the same unit. Because the transformer is carried by the column, the separate CT pedestal with its own primary connections and its own earthing disappears from the pole. Zero-sequence transformers and voltage sensors can be added alongside for an earth-fault and voltage-measurement scheme.

Isolating switch and interlock

Where a visible break is required, an isolating switch is added as a separate blade assembly on the same frame rather than by combining it with the interrupter. The switch is mechanically interlocked with the breaker so that it cannot be operated while the breaker is closed, and the interlock holds with the control supply removed.

Automation and remote control

With a controller mounted on the frame, the ZW32 works as an automated sectioning or reclosing point. Remote measurement, remote signalling, remote control and remote adjustment are carried over the controller communication port, so the utility can see and operate the switch from the control centre. Closing back onto a transient fault and isolating a faulted span are both supported. The same controller is used across all three voltage classes, so an operator who knows the 12 kV installation already knows the 40.5 kV one.

Application as a boundary switch

At the demarcation point between a utility network and a customer installation, the breaker with a controller acts as the boundary switch: it isolates the customer fault from the utility feeder and reports it, so a fault inside the customer installation does not take out the whole line. This is one of the most common duties for a pole-mounted vacuum breaker at any of the three voltage classes.

Selecting A ZW32 For Your Network

The three classes overlap in current and in breaking rating, so the choice is made on the system voltage and on what the network has to do, not on the physical size of the breaker.

10 kV systems — the 12 kV class

This is the standard answer for a 10 kV overhead network, and it is also the class in which the widest range of ratings is available. One platform covers line switching, transformer incomer protection, boundary metering and automated sectioning; specify 20 kA unless the utility fault-level calculation says otherwise, and 25 kA where the network is stiff or is being reinforced.

20 kV systems — the 24 kV class

Specified when a 10 kV network is uprated to carry more load over the same right of way, and on networks that were built at 20 kV from the start. The phase spacing widens to 380 mm and the interrupter assembly is larger, which is what the higher system short-circuit level of a 20 kV network requires. Current transformers, the isolator and the controller are the same items as in the 12 kV class.

35 kV systems — the 40.5 kV class

The same compact construction carried up to 40.5 kV, instead of the porcelain-column arrangement conventionally used at this level. It is supplied from 630 A to 1600 A with breaking capacity to 31.5 kA, and its weight and footprint make pole and platform mounting practical where a porcelain-column breaker would need a substantially heavier structure.

Confirming the class before quoting

If the class is not yet fixed, send the system voltage, the maximum and minimum load current and the fault level at the point of installation. We will confirm the class, the current rating and the breaking capacity, and state which of the two applies before a price is put on the enquiry.

Key Features

One Platform, Three Voltage Classes The 12 kV, 24 kV and 40.5 kV classes share the column construction, the spring mechanism and the frame drawing. A utility that standardises on the ZW32 keeps one spare-parts list, one operating procedure and one set of test records across a 10 kV, a 20 kV and a 35 kV network.
Separate Columns Instead Of A Common Tank Each phase has its own interrupter column and its own dielectric clearance to the other phases. That gives the ZW32 its breaking capability and its clearly separated phase spacing at every class, and it lets one phase interrupter be replaced without disturbing the other two.
Solid Insulation, No Oil And No Gas The interrupter is held in a cast epoxy cylinder with cast-in or silicone-covered sheds, and it breaks in vacuum. There is no insulating liquid to test and no insulating gas to monitor, so the breaker needs no periodic insulation maintenance, only a visual check and an operating test.
Built-In Current Transformers On The Columns The CT rings sit around the primary connection at the top of each interrupter column. Metering and protection can be taken from the same breaker, and the separate CT pedestal with its own primary connections and earthing is no longer mounted on the pole.
Optional Isolating Function With Visible Break The G version provides an isolating distance that meets the across-the-gap withstand values given above, with the position shown by the mechanism and mechanically interlocked with the breaker. That makes the unit usable as a sectioning point in its own right.
Short Operating Times Opening time is 50 ms or less and closing time 60 ms or less in the 12 kV and 24 kV classes, with the three poles operating together within 2 ms. Contact bounce on closing is 2 ms or less, which keeps contact erosion low and helps the interrupter reach its rated number of operations.
Anti-Condensation Outdoor Construction The interrupter columns, the linkage and the mechanism box are designed to resist condensation in humid, polluted and coastal environments, and an anti-condensation heater is available for the mechanism box. The external insulation is selected against the pollution class at the enquiry stage.
Routine-Tested Before Dispatch Every breaker passes main-circuit resistance measurement, a power-frequency withstand test of the main and auxiliary circuits, a contact-gap and overtravel check and a full mechanical operating sequence before dispatch. The test records travel with the breaker.

Applications

The ZW32 is used wherever a 10 kV, 20 kV or 35 kV network has to be switched outdoors — on the overhead line, at a pole substation, or at the incoming point of an industrial installation.

  • 10 kV, 20 kV and 35 kV overhead distribution lines — line switching and isolation
  • Sectioning points and sectionalising switches on feeders of all three classes
  • Pole-mounted and platform substations — transformer incomer protection
  • Boundary switches at the utility-to-customer demarcation point
  • Rural and urban network upgrades, including 10 kV to 20 kV uprating
  • Branch lines and teed connections — fault isolation at the branch
  • Industrial and mining installations — outdoor plant incomers
  • Renewable plant collector lines — switching at the plant edge
  • Wind and solar farms — collector feeder protection
  • Water supply and pumping stations — outdoor pump feeder switching
  • Utility distribution automation — automated sectioning and reclosing points
  • Temporary and emergency supply — rapid restoration after storm damage

What We Need to Quote Your Breaker

The breaker is configured to the line, the pole and the automation requirement. With the items below we can return a firm quotation, the frame drawing and the controller interface list.

  • System voltage and rated frequency, 50 or 60 Hz
  • Maximum and minimum load current, and the fault level at the point of installation
  • The voltage class required, if that is already fixed
  • Whether an isolating function or a visible break is required
  • Current transformer requirement — quantity, ratio and accuracy class
  • Automation requirement — plain breaker, sectionaliser or boundary switch
  • Control voltage available and whether a voltage transformer is needed
  • Site conditions — altitude, minimum temperature, ice, pollution, wind

Send these to gohointl@gmail.com and we will reply with a priced offer, the outline drawing for the pole or platform frame, the secondary circuit diagram and the routine test plan for the breaker.

Standards & Documentation

ItemReference
Product standard, ChinaGB/T 1984 — High-voltage alternating-current circuit-breakers
Common specification, ChinaGB/T 11022 — Common specifications for high-voltage switchgear and controlgear
Vacuum circuit breaker standard, ChinaJB/T 3855 — High-voltage alternating-current vacuum circuit-breakers
Typical technical conditions, ChinaDL/T 402 — Specification of high-voltage alternating-current circuit-breakers
Insulation coordination, ChinaGB 311.1 — Insulation coordination for high-voltage transmission and transformation equipment
Long-term heating, ChinaGB 763 — Heating of AC high-voltage electrical equipment under long-term operation
Product standard, internationalIEC 62271-100 — High-voltage switchgear and controlgear, Part 100
Routine test, main circuitMain circuit resistance measurement and power-frequency withstand test
Routine test, auxiliary circuitsWiring check and power-frequency withstand test of the control and auxiliary circuits
Routine test, mechanicalContact gap and overtravel check, then a full open and close operating sequence
Documentation suppliedOutline drawing for the pole or platform frame, secondary circuit diagram, routine test record and operating instructions

Type test reports for the ZW32 platform and the routine test record for the individual breaker are available for project qualification on request.

ZW32 series intelligent outdoor vacuum circuit breaker on its mounting frame, arranged as an automated sectioning point with the controller mounted alongside.
Intelligent sectioning configuration. The three-column breaker with the controller on the same frame. In this arrangement the unit sections the line at the faulted span, closes back onto a transient fault and reports the operation to the control centre over the controller communication port.

Breakers are assembled in our own factory in Yueqing, Zhejiang — the same site that builds our switchgear, transformers and prefabricated substations. Column casting, interrupter fitting, linkage alignment, wiring and routine testing all happen in‑house, which keeps both the delivery schedule and the quality check inside our control.

Need a ZW32 breaker between 10 kV and 40.5 kV?
Get a Quote

GOHO® is a registered trademark of Gonghong Electric Appliance Co., Ltd. Technical data describes the standard ZW32 outdoor vacuum circuit breaker platform across the 12 kV, 24 kV and 40.5 kV classes and is given as typical ratings; the ratings of a specific unit follow the approved drawing and the configuration ordered. Ratings outside the table in this page, and site conditions outside the stated limits, are quoted on application. Product images are shown for illustration. Please refer to the drawing issued with your offer for dimensional and foundation data.